Back to the backflow review queue
Backflow assembly test: 7680 Sycamore Trl
ApprovedFiled Feb 11, 2026 by Jordan Nguyen, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 11, 2026
- Assembly type
- RP
- Serial number
- K718173
- Size
- 3/4
- Test gauge serial
- G-6644
- Gauge calibration date
- Oct 1, 2025
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Nguyen, current on the service date
- All required fields present
- Address matches parcel 085-48-01230
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7680 Sycamore Trl
Owner: Rowan Pruitt
Parcel 085-48-01230