Backflow assembly test: Crossroads Animal Hospital

Approved

Filed Jun 14, 2025 by Reese Calloway, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jun 14, 2025
Assembly type
RP
Serial number
B151725
Size
2
Test gauge serial
G-5468
Gauge calibration date
Mar 16, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 085-61-01027
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.