Back to the backflow review queue

Backflow assembly test: 3573 Spring Branch Ln

Approved

Filed Jan 7, 2026 by Hayden Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 7, 2026
Assembly type
RP
Serial number
K951859
Size
3/4
Test gauge serial
G-1136
Gauge calibration date
Apr 17, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 085-54-01086
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3573 Spring Branch Ln
Owner: Riley Kessler
Parcel 085-54-01086