Backflow assembly test: Two Rivers Apartments
ApprovedFiled Nov 6, 2026 by Logan Danner, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 6, 2026
- Assembly type
- RP
- Serial number
- W300730
- Size
- 2
- Test gauge serial
- G-9455
- Gauge calibration date
- Apr 15, 2026
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Danner, current on the service date
- All required fields present
- Address matches parcel 085-37-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.