Back to the backflow review queue
Backflow assembly test: Golden Animal Hospital
ApprovedFiled Mar 25, 2026 by Hayden Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 25, 2026
- Assembly type
- RP
- Serial number
- K800193
- Size
- 1
- Test gauge serial
- G-8136
- Gauge calibration date
- Jun 16, 2025
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Lindqvist, current on the service date
- All required fields present
- Address matches parcel 085-32-01326
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4954 Meadow Lark Rd
Owner: Ellery Holdings LLC
Parcel 085-32-01326