Backflow assembly test: 2979 Turkey Hill Ln

Approved

Filed Jul 20, 2026 by Jordan Nguyen, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 20, 2026
Assembly type
RP
Serial number
A897660
Size
1
Test gauge serial
G-8250
Gauge calibration date
May 31, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-74-01116
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.