Backflow assembly test: Crossroads Brewing Co
ApprovedFiled May 24, 2024 by Logan Danner, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 24, 2024
- Assembly type
- RP
- Serial number
- K700016
- Size
- 4
- Test gauge serial
- G-9732
- Gauge calibration date
- Oct 19, 2023
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Danner, current on the service date
- All required fields present
- Address matches parcel 085-91-01146
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
7742 Pine Knoll Way
Owner: Marsh Holdings LLC
Parcel 085-91-01146