Back to the backflow review queue

Backflow assembly test: Crossroads Brewing Co

Approved

Filed May 26, 2026 by Logan Danner, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 26, 2026
Assembly type
RP
Serial number
K700016
Size
4
Test gauge serial
G-1541
Gauge calibration date
Dec 28, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Danner, current on the service date
  • All required fields present
  • Address matches parcel 085-91-01146
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7742 Pine Knoll Way
Owner: Marsh Holdings LLC
Parcel 085-91-01146