Backflow assembly test: Hilltop Medical Offices

Approved

Filed Oct 9, 2025 by Cameron Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 9, 2025
Assembly type
RP
Serial number
A567074
Size
2
Test gauge serial
G-6450
Gauge calibration date
Jun 28, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-93-01004
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4968 Hickory Ct
Owner: Whitcomb Holdings LLC
Parcel 085-93-01004