Back to the backflow review queue

Backflow assembly test: Hilltop Medical Offices

Approved

Filed Nov 13, 2026 by Logan Danner, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 13, 2026
Assembly type
RP
Serial number
A567074
Size
2
Test gauge serial
G-9708
Gauge calibration date
Aug 8, 2026
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Danner, current on the service date
  • All required fields present
  • Address matches parcel 085-93-01004
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4968 Hickory Ct
Owner: Whitcomb Holdings LLC
Parcel 085-93-01004