Backflow assembly test: Riverside Market
ApprovedFiled Aug 7, 2025 by Cameron Nguyen, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 7, 2025
- Assembly type
- DC
- Serial number
- B312494
- Size
- 1 1/2
- Test gauge serial
- G-1942
- Gauge calibration date
- Jun 13, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Nguyen, current on the service date
- All required fields present
- Address matches parcel 085-25-01280
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.