Backflow assembly test: 6678 Sycamore Trl

Approved

Filed Nov 11, 2026 by Sam Benton, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Nov 11, 2026
Assembly type
RP
Serial number
A674233
Size
3/4
Test gauge serial
G-7996
Gauge calibration date
Jun 8, 2026
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Benton, current on the service date
  • All required fields present
  • Address matches parcel 093-18-01300
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6678 Sycamore Trl
Owner: Shawn Okafor
Parcel 093-18-01300