Back to the backflow review queue

Backflow assembly test: 7647 Fox Run Way

Approved

Filed Nov 26, 2023 by Emerson Calloway, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Nov 26, 2023
Assembly type
RP
Serial number
K224487
Size
1
Test gauge serial
G-3297
Gauge calibration date
Mar 31, 2023
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 093-19-01032
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.