Backflow assembly test: 1627 Orchard Trl
ApprovedFiled Apr 14, 2026 by Reese Hollins, Lakeside Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 14, 2026
- Assembly type
- PVB
- Serial number
- W537821
- Size
- 3/4
- Test gauge serial
- G-6703
- Gauge calibration date
- Jun 9, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Hollins, current on the service date
- All required fields present
- Address matches parcel 093-40-01344
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1627 Orchard Trl
Owner: Rowan Hollins
Parcel 093-40-01344