Back to the backflow review queue
Backflow assembly test: 4781 Fox Run Way
ApprovedFiled Jun 15, 2023 by Sam Benton, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 15, 2023
- Assembly type
- RP
- Serial number
- Z946884
- Size
- 1
- Test gauge serial
- G-8858
- Gauge calibration date
- Sep 21, 2022
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Benton, current on the service date
- All required fields present
- Address matches parcel 093-22-01079
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4781 Fox Run Way
Owner: Drew Marsh
Parcel 093-22-01079