Backflow assembly test: 5443 Quarry Ct

Approved

Filed Oct 1, 2024 by Emerson Calloway, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 1, 2024
Assembly type
PVB
Serial number
B279649
Size
1
Test gauge serial
G-3950
Gauge calibration date
Aug 19, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 093-21-01305
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5443 Quarry Ct
Owner: Jordan Okafor
Parcel 093-21-01305