Backflow assembly test: 1149 Quarry Ln

Approved

Filed Mar 7, 2025 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 7, 2025
Assembly type
RP
Serial number
B446842
Size
3/4
Test gauge serial
G-9051
Gauge calibration date
Mar 2, 2024
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Relief valve opened at
2.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 093-28-01052
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1149 Quarry Ln
Owner: Jamie Whitcomb
Parcel 093-28-01052