Backflow assembly test: 141 Stone Gate Ln
ApprovedFiled Aug 16, 2026 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 16, 2026
- Assembly type
- RP
- Serial number
- Z280360
- Size
- 3/4
- Test gauge serial
- G-7421
- Gauge calibration date
- Mar 6, 2026
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-32-01352
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.