Back to the backflow review queue

Backflow assembly test: Station Medical Offices

Approved

Filed May 14, 2025 by Morgan Brandt, Lakeside Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 14, 2025
Assembly type
RP
Serial number
B896901
Size
1 1/2
Test gauge serial
G-3772
Gauge calibration date
Sep 2, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-31-01356
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9222 Stone Gate Ln
Owner: Nguyen Holdings LLC
Parcel 093-31-01356