Backflow assembly test: 7685 Orchard Ct
ApprovedFiled Dec 23, 2025 by Drew Vance, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 23, 2025
- Assembly type
- RP
- Serial number
- B255066
- Size
- 3/4
- Test gauge serial
- G-6511
- Gauge calibration date
- Nov 11, 2025
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-36-01024
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7685 Orchard Ct
Owner: Parker Kessler