Backflow assembly test: Two Rivers Pizza

Approved

Filed Jan 5, 2024 by Reese Hollins, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Jan 5, 2024
Assembly type
DC
Serial number
B699657
Size
1
Test gauge serial
G-2857
Gauge calibration date
May 29, 2023
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Hollins, current on the service date
  • All required fields present
  • Address matches parcel 093-12-01176
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5466 Spring Branch Trl
Owner: Marsh Holdings LLC
Parcel 093-12-01176