Back to the backflow review queue

Backflow assembly test: 2097 Mill Creek Rd

Approved

Filed Aug 18, 2026 by Reese Hollins, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Aug 18, 2026
Assembly type
RP
Serial number
A559673
Size
1
Test gauge serial
G-3034
Gauge calibration date
Apr 12, 2026
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Hollins, current on the service date
  • All required fields present
  • Address matches parcel 093-18-01171
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2097 Mill Creek Rd
Owner: Rowan Nguyen
Parcel 093-18-01171