Back to the backflow review queue

Backflow assembly test: Corner Diner

Approved

Filed Apr 13, 2026 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Apr 13, 2026
Assembly type
RP
Serial number
W842401
Size
2
Test gauge serial
G-6948
Gauge calibration date
Jan 30, 2026
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-82-01042
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1679 Hickory Ln
Owner: Benton Holdings LLC
Parcel 093-82-01042