Back to the backflow review queue

Backflow assembly test: 2429 Old Church Way

Approved

Filed Jan 14, 2024 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 14, 2024
Assembly type
PVB
Serial number
A279159
Size
3/4
Test gauge serial
G-4293
Gauge calibration date
Sep 29, 2023
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 093-58-01212
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2429 Old Church Way
Owner: Jamie Ashby
Parcel 093-58-01212