Backflow assembly test: 6406 Sycamore Ct

Approved

Filed Mar 18, 2025 by Morgan Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Mar 18, 2025
Assembly type
PVB
Serial number
W694698
Size
1
Test gauge serial
G-5017
Gauge calibration date
Apr 6, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Benton, current on the service date
  • All required fields present
  • Address matches parcel 095-36-01321
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6406 Sycamore Ct
Owner: Cameron Kessler
Parcel 095-36-01321