Back to the backflow review queue
Backflow assembly test: 7326 Cedar Hollow Trl
ApprovedFiled Dec 12, 2024 by Rowan Danner, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 12, 2024
- Assembly type
- DC
- Serial number
- Z768307
- Size
- 3/4
- Test gauge serial
- G-7127
- Gauge calibration date
- May 7, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Danner, current on the service date
- All required fields present
- Address matches parcel 095-13-01192
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7326 Cedar Hollow Trl
Owner: Rowan Benton
Parcel 095-13-01192