Backflow assembly test: 9261 Spring Branch Trl
ApprovedFiled Sep 6, 2025 by Drew Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 6, 2025
- Assembly type
- PVB
- Serial number
- Z114446
- Size
- 3/4
- Test gauge serial
- G-9071
- Gauge calibration date
- Jan 12, 2025
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Nguyen, current on the service date
- All required fields present
- Address matches parcel 095-17-01148
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.