Backflow assembly test: Riverside Dental

Approved

Filed Feb 19, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 19, 2026
Assembly type
DC
Serial number
W950120
Size
2
Test gauge serial
G-8839
Gauge calibration date
Dec 3, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-32-01343
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6214 Spring Branch Dr
Owner: Calloway Holdings LLC
Parcel 095-32-01343