Backflow assembly test: Two Rivers Grill

Filed Nov 20, 2026 by Reese Whitcomb, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 20, 2026
Assembly type
RP
Serial number
K199949
Size
2
Test gauge serial
G-9685
Gauge calibration date
May 9, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 095-97-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.