Backflow assembly test: 3308 Mill Creek Ct

Approved

Filed Sep 24, 2024 by Rowan Danner, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Sep 24, 2024
Assembly type
RP
Serial number
W527658
Size
1
Test gauge serial
G-3684
Gauge calibration date
Feb 13, 2024
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Danner, current on the service date
  • All required fields present
  • Address matches parcel 095-67-01190
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3308 Mill Creek Ct
Owner: Riley Ashby
Parcel 095-67-01190