Back to the backflow review queue
Backflow assembly test: Two Rivers Bakery
ApprovedFiled Dec 21, 2025 by Quinn Vance, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 21, 2025
- Assembly type
- DC
- Serial number
- K498117
- Size
- 1 1/2
- Test gauge serial
- G-9007
- Gauge calibration date
- Jul 20, 2025
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Vance, current on the service date
- All required fields present
- Address matches parcel 095-34-01337
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3582 Stone Gate Ln
Owner: Ramirez Holdings LLC
Parcel 095-34-01337