Back to the backflow review queue

Backflow assembly test: 3308 Mill Creek Ct

Approved

Filed Oct 21, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 21, 2026
Assembly type
RP
Serial number
W527658
Size
1
Test gauge serial
G-8945
Gauge calibration date
Mar 30, 2026
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-67-01190
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3308 Mill Creek Ct
Owner: Riley Ashby
Parcel 095-67-01190