Backflow assembly test: 3268 Cedar Hollow Ln

Approved

Filed Jul 19, 2026 by Morgan Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jul 19, 2026
Assembly type
DC
Serial number
W441645
Size
1
Test gauge serial
G-5791
Gauge calibration date
Apr 18, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Benton, current on the service date
  • All required fields present
  • Address matches parcel 095-51-01355
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3268 Cedar Hollow Ln
Owner: Cameron Fairley
Parcel 095-51-01355