Backflow assembly test: 8614 Sycamore Ct

Approved

Filed Oct 14, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 14, 2026
Assembly type
PVB
Serial number
A507540
Size
1
Test gauge serial
G-8990
Gauge calibration date
Aug 8, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
1.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-47-01155
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8614 Sycamore Ct
Owner: Drew Danner
Parcel 095-47-01155