Backflow assembly test: Maple Leaf Elementary School

Approved

Filed Sep 15, 2024 by Rowan Danner, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Sep 15, 2024
Assembly type
RP
Serial number
W967874
Size
4
Test gauge serial
G-3818
Gauge calibration date
Mar 17, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Danner, current on the service date
  • All required fields present
  • Address matches parcel 095-72-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.