Back to the backflow review queue

Backflow assembly test: 1380 Pine Knoll Trl

Approved

Filed May 25, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 25, 2026
Assembly type
RP
Serial number
A727355
Size
3/4
Test gauge serial
G-3019
Gauge calibration date
Apr 17, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-13-01081
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1380 Pine Knoll Trl
Owner: Blake Ellery
Parcel 095-13-01081