Backflow assembly test: Golden Elementary School
Needs reviewFiled Nov 24, 2026 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- W175330
- Size
- 2
- Test gauge serial
- G-6985
- Gauge calibration date
- Jun 10, 2026
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ashby, current on the service date
- All required fields present
- Address matches parcel 095-99-01066
- Readings in range, no flags
- Result: passing. Next due date resets when approved.