Backflow assembly test: 1756 Cedar Hollow Ln
ApprovedFiled Mar 24, 2024 by Taylor Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 24, 2024
- Assembly type
- RP
- Serial number
- B705391
- Size
- 3/4
- Test gauge serial
- G-7353
- Gauge calibration date
- Nov 29, 2023
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Whitcomb, current on the service date
- All required fields present
- Address matches parcel 097-60-01190
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1756 Cedar Hollow Ln
Owner: Blake Brandt
Parcel 097-60-01190