Back to the backflow review queue

Backflow assembly test: 3291 Sycamore Rd

Approved

Filed Aug 27, 2025 by Alex Kessler, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 27, 2025
Assembly type
RP
Serial number
A385500
Size
1
Test gauge serial
G-6961
Gauge calibration date
Feb 14, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-27-01050
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3291 Sycamore Rd
Owner: Taylor Ellery
Parcel 097-27-01050