Back to the backflow review queue

Backflow assembly test: 7733 Pine Knoll Rd

Approved

Filed Feb 22, 2024 by Alex Kessler, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 22, 2024
Assembly type
RP
Serial number
K440439
Size
1
Test gauge serial
G-8110
Gauge calibration date
Jul 24, 2023
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-45-01059
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7733 Pine Knoll Rd
Owner: Logan Pruitt
Parcel 097-45-01059