Backflow assembly test: 8528 Spring Branch Way

Approved

Filed Nov 16, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 16, 2026
Assembly type
PVB
Serial number
A471960
Size
1
Test gauge serial
G-6845
Gauge calibration date
Jul 25, 2026
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-63-01036
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.