Backflow assembly test: 4355 Mill Creek Rd
ApprovedFiled Feb 3, 2025 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 3, 2025
- Assembly type
- DC
- Serial number
- B534505
- Size
- 3/4
- Test gauge serial
- G-3517
- Gauge calibration date
- May 10, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-87-01039
- Readings in range, no flags
- Result: passing. Next due date resets when approved.