Back to the backflow review queue
Backflow assembly test: Golden Self Storage
ApprovedFiled Feb 22, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 22, 2026
- Assembly type
- RP
- Serial number
- K833945
- Size
- 2
- Test gauge serial
- G-4264
- Gauge calibration date
- Jan 10, 2026
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-74-01303
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3311 Stone Gate Way
Owner: Ellery Holdings LLC
Parcel 097-74-01303