Back to the backflow review queue

Backflow assembly test: Golden Self Storage

Approved

Filed Feb 22, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 22, 2026
Assembly type
RP
Serial number
K833945
Size
2
Test gauge serial
G-4264
Gauge calibration date
Jan 10, 2026
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-74-01303
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3311 Stone Gate Way
Owner: Ellery Holdings LLC
Parcel 097-74-01303