Backflow assembly test: Station Medical Offices

Approved

Filed Apr 13, 2026 by Taylor Whitcomb, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 13, 2026
Assembly type
DC
Serial number
B215560
Size
1
Test gauge serial
G-6562
Gauge calibration date
Jan 27, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 097-14-01330
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.