Backflow assembly test: 2275 Meadow Lark Trl

Approved

Filed Dec 13, 2024 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 13, 2024
Assembly type
RP
Serial number
K812510
Size
1
Test gauge serial
G-1286
Gauge calibration date
Oct 4, 2024
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-45-01255
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2275 Meadow Lark Trl
Owner: Jordan Calloway
Parcel 097-45-01255