Back to the backflow review queue

Backflow assembly test: 2275 Meadow Lark Trl

Approved

Filed Dec 24, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 24, 2025
Assembly type
RP
Serial number
K812510
Size
1
Test gauge serial
G-8829
Gauge calibration date
Jun 18, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-45-01255
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2275 Meadow Lark Trl
Owner: Jordan Calloway
Parcel 097-45-01255