Back to the backflow review queue

Backflow assembly test: Golden Bakery

Approved

Filed Jan 10, 2026 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jan 10, 2026
Assembly type
RP
Serial number
W657995
Size
4
Test gauge serial
G-1645
Gauge calibration date
Dec 11, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 097-98-01308
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1639 Orchard Ln
Owner: Kessler Holdings LLC
Parcel 097-98-01308