Back to the backflow review queue

Backflow assembly test: 4281 Meadow Lark Way

Approved

Filed Nov 6, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 6, 2025
Assembly type
RP
Serial number
K304845
Size
1
Test gauge serial
G-7942
Gauge calibration date
Feb 3, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-10-01334
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4281 Meadow Lark Way
Owner: Quinn Fairley
Parcel 097-10-01334