Back to the backflow review queue

Backflow assembly test: 595 Pine Knoll Ln

Approved

Filed Jun 30, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 30, 2026
Assembly type
RP
Serial number
B722332
Size
3/4
Test gauge serial
G-7916
Gauge calibration date
Mar 9, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-23-01321
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

595 Pine Knoll Ln
Owner: Shawn Stroud
Parcel 097-23-01321