Back to the backflow review queue
Backflow assembly test: Main Street Animal Hospital
Sent backFiled Nov 23, 2026 by Drew Okafor, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- DC
- Serial number
- Z318426
- Size
- 2
- Test gauge serial
- G-3360
- Gauge calibration date
- Feb 26, 2026
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Okafor, current on the service date
- All required fields present
- Address matches parcel 097-26-01311
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
7527 Mill Creek Ln
Owner: Hollins Holdings LLC
Parcel 097-26-01311